Type X vs. Type C Drywall

Updated

Short answer

Type X is fire-rated gypsum board defined by ASTM C1396: 5/8 inch Type X gives at least a 1-hour rating in the standard test wall. Type C is an improved Type X with more glass fiber and additives that hold the core together longer in a fire. Use the type the fire-rated design names; Type C is most often required in ceilings and floor-ceiling assemblies.

The Difference

Type XType C
Defined byASTM C1396Manufacturers, as an improved Type X. It also meets the Type X definition
CoreGypsum with glass fibersGypsum with more glass fibers and additives that expand with heat to offset shrinkage
Common thicknesses5/8", also 1/2"1/2" and 5/8"
Tested rating5/8": at least 1 hour, and 1/2": at least 45 minutes, on the standard wood-stud test wallRated by the assemblies it is listed in
Usually required for1-hour and 2-hour walls and partitions, corridors, shaft enclosuresCeilings, floor-ceiling and roof-ceiling assemblies, and wall designs that list it

Board shrinks as fire drives the water out of the gypsum. On a ceiling that shrinkage opens the joints and the board falls sooner, which is why ceiling assemblies so often list Type C.

Which One the Wall Needs

  1. Find the fire-rated design on the drawings: a UL design number such as U419, or a Gypsum Association file number.
  2. Read the board that design lists. It gives the type, the thickness and the number of layers.
  3. Order that board. A design that lists Type C needs Type C. A design that lists Type X may also accept Type C, but only if the listing says so.

A fire rating belongs to the whole tested assembly: the board, the studs, their spacing, the fasteners and the insulation. Changing one part can void the rating.

Fire-Rated Boards in the Catalog

CertainTeed fire-rated gypsum board
BoardThicknessUse
Type X Drywall5/8"5/8" fire-rated, the commercial standard
Type C DrywallSee data sheetWhere the assembly calls for Type C
FireLITE® Type X5/8"Lighter Type X, same fire rating
RipRoc™ Type X Drywall PanelSee data sheetType X that scores and snaps clean
GlasRoc® Shaftliner Type X1"1" shaftliner with a fiberglass mat face
M2Tech® Shaftliner Type X1"1" paper-faced shaftliner, mold resistant

Every board's page has CertainTeed's data sheet and fire-resistance documents. See all drywall.

Common Questions

What is the difference between Type X and Type C drywall?
Both are fire-rated gypsum board. Type X is the standard defined by ASTM C1396. Type C is an improved Type X whose core has more glass fiber and additives that expand with heat, so it holds together longer in a fire. Type C is most often required in ceilings and floor-ceiling assemblies.
Is Type C drywall better than Type X?
Type C performs longer in a fire test than Type X of the same thickness, but the board to use is the one the fire-rated design lists. A design tested with Type X does not need Type C.
Can Type X be used instead of Type C?
No, not where the fire-rated design lists Type C. The rating applies only to the board the assembly was tested with.
Is 5/8 inch drywall always Type X?
No. Most 5/8 inch board sold for commercial work is Type X, but 5/8 inch board is also made without a Type X core. Check for the Type X marking on the board and the data sheet.
How long does Type X drywall resist fire?
On the standard ASTM test wall, a single layer of 5/8 inch Type X on each side gives at least a 1-hour rating, and 1/2 inch Type X gives at least 45 minutes. Real ratings depend on the full tested assembly.

Order it

Stock lengths or cut to your exact size, priced before you send the order. Not sure what the job takes? Send the plans and we will send back a material list.

Sources

Figures are the manufacturers’ published values and the catalog’s own data. The project drawings, specifications and the engineer of record govern what a job requires.